CHARNAUD® SURVIVE-ARC® Body protection.
- Arc flash switching suit, with thermal liner for protection against arc flash, hot or burning
transformer oil and corrosive liquids. - Three-piece suit consisting of jacket, bib-and-brace trousers and ventilated hood. Arc rating of
ATPV 60 cal/cm² indicated on garments and hood. - Jacket: Long jacket with FR zip, FR Velcro® front closure and hemmed cuffs with strap and FR
Velcro closure. - Trousers: Bib-and-brace trousers with width adjustment on hips and leg openings.
- Switching hood: One piece ventilated shaped hood with large transparent lens with improved
optical correctness, attached to internal dielectric hard hat with chinstrap. - Mitts: See separate Product Information sheet.
- Options:
• Company embroidery as required.
• ATEX zone 2/22 (II 3 GD Ex nA ic IIB T4 Gc tc IIIC T135°C Dc) certified headlamp for
use in explosive environments, offers 60 lumens at 15m for 3h30 on hoods.
COLOUR : Navy
Hood: One size fits all. Hard hat with adjustable head size.
MATERIALS :
- FR/AR liquid proof outer with FR liner.
- Face shield: Dual pane, transparent with improved optical correctness, anti-fog.
APPLICATION : Arc flash protective work wear for the electrical industry, including the presence of hot/burring transformer oil and corrosive liquids.
HAZARD ASSESSMENTS
Thermal effects from arc flash and presence of flammable/hot transformer oil and corrosive liquids.
FEATURES
- Liquid and chemical proof FR/AR outer fabric with sealed seams.
- Exceptional insulation from high heat loads.
- Thermal liner has excellent breath-ability with moisture/sweat absorption and dissipation.
- Water washable.
STANDARDS : Fabric and/or garment:
- NFPA 70E.
- ASTM F2621.
- ASTM F2178.
- IEC 61482-2.
- SANS 724.
- ASTM F1930 – Body burn percentage: 0%, excluding head, hands and feet.
- ATPV¹: 66 cal/cm²; HAF²: 95 %